![]() ![]() ![]() Accurate calculation of fault currents is of great importance for the right dimensioning of transformer secondary winding protection. Since each phase winding in zigzag (z) connection couples two core limbs, it makes the calculation of transformer reactance and adding the power system network reactance into calculations of fault currents more difficult. Zig-zag connected winding is less frequent and therefore less known. Transformers with star-connected LV winding and earthed neutral represent a majority of transformers produced or in use today. Dokazuje se, da u sva tri navedena slučaja struje jednopolnog i struje tropolnog kratkog spoja i prateća naprezanja materijala ne ovise o spoju primarnog namota nego samo o geometriji namota i reaktanciji mreže. ![]() U radu se obrađuje račun struja jednopolnog i tropolnog kratkog spoja na sekundaru transformatora u spoju Dzn, Yzn i YNzn napajanih iz mreže poznatog unutrašnjeg otpora, kakav obično traže kupci takvih transformatora. Točan račun struja kvara važan je za ispravno dimenzioniranje sekundarne zaštite transformatora. Budući da svaki fazni namot u spoju slomljena zvijezda ili cik-cak (oznaka z) ulančuje namote s dva stupa, složeniji je i račun reaktancija transformatora i uklapanje reaktancija mreže u račun struja kvara. Nisko naponski namoti transformatora u spoju zvijezda s izvedenom nultočkom nekako su se udomaćili u proizvodnji i u upotrebi transformatora, dok namoti u spoju slomljena zvijezda nisu tako česti ni opće poznati. ![]()